Wireless I/O
|
DAX6500
|
|||||
Features
|
The Data-Linc Group DAX6500 I/O extender offers the ability to transmit discrete and analog signals with robust, industrial wireless technology. This allows wireless I/O communication between the Master and one or more Remotes from a few feet to many miles with applications in many industries. For added convenience, any unit may be configured as Master, Remote, Repeater or Repeater/Remote. This not only simplifies replacement but also reduces the number of units needed for spare inventory. A further convenience is the use of pluggable terminal blocks. If a unit needs to be replaced, unplug the terminal block with all its connecting wires and simply plug it into the replacement unit, eliminating the need to reconnect each individual wire.
The DAX6500 offers 12 bit analog resolution for enhanced accuracy and resolution of the analog channels. It therefore provides more precise monitoring and control, allowing data collected at the input to be relayed and reported with greater accuracy to the Master. For confidence in the wireless network’s performance, the DAX is capable of utilizing Data-Linc’s powerful, proprietary LincViewTM OPC RF network diagnostics and management software (see LincView OPC data sheet for information).
Each DAX6500 has a total of 24 independent points— eight discrete inputs and eight discrete outputs, as well as four analog inputs and four analog outputs. The SRM6x20 radio component reliably relays data even in harsh industrial environments. But in the event of a communications failure, the output states of the discrete and analog channels can be configured to retain the last known value or a pre-defined state.
The DAX6500 is ideal for fixed or mobile installations. Its wireless component combines the analog and discrete I/O extender with Data-Linc Group’s SRM industrial grade license-free wireless modems. In addition to the DAX6500 2.4 GHz (up to 10 miles, 16 km with LOS) and the DAX6400 900 MHz versions, the DAX/EXP expansion non radio Remote is also an option. The result is a simple to implement solution for wireless I/O signal transmission that ensures solid performance and reliability in any RF or wire environment. It is also ARRA compliant.
* American Recovery and Reinvestment Act of 2009
Download pdf (720K) the printable version of the Data Sheet for the DAX6500 Discrete/Analog I/O Extender. (Requires Adobe Acrobat Reader to open.)
^ Top of Page ^
Included
CD.Configuration software, LincViewTM OPC RF network management software, User Manual
Antenna. 0 dB bench test antenna
Other. Programming cable, power supply
Operating ranges
System gain. 134 dB
Distance. 10 miles (16 km) LOS with omni antennas
Transmitter
RF Output Power. 500mW maximum, (10 programmable steps)
Modulation. FHSS, GFSK
Hop Patterns. 15 (user selectable)
Occupied Bandwidth. 230KHz
Error Correction. 32 bit CRC
RF Encryption. Substitution Dynamic Key
Receiver
Sensitivity. -107 dBm @ 10-4 raw BER
Selectivity. 40 dB @ fc ±230 KHz and 60dB @ fc ±460 KHz
Channel Functions
Analog. Analog. 0-20ma, 4-20mA or 0-10 VDC, 24VDC max. loop voltage, 12 bit resolution. Self-powered outputs.
Discrete Input. Dry contact closure
Discrete Output. Open collector (sink to ground), 100mA per channel, 12-24VDC
Connections
Antenna. Standard thread female SMA for optional
external omni directional or yagi antennas.
I/O Discrete and Analog Detachable screw-type terminal blocks
Wire size 12-26 AWG
Power. Detachable three position screw terminal block
Configuration port. Standard DB9 RS232 port
EX-Linc. DB9 RS232 or RS485 2-wire
Indicators
General.
P. Power
C. Carrier Detect
I. RF input
O. RF output
Comm Error
Discrete. Activity LED for each discrete I/O
Power
Voltage. 12-28VDC nominal
Current. 160mA idle, 660mA peak on transmit
Operating Environment
Standard. -40°0 to 167° F (-40° to 75° C)
Humidity. 0 to 95% non-condensing humidity
Enclosure
Standard. 18-gauge steel with mounting flanges
3.0 in x 2.75 x 8.1 in (7.6 x 7 x 20.6 cm)
Optional. DIN rail mounting
Shipping Weight. 1.8 lb (0.82 kg)
* Backward compatibility with DDAA legacy products for certain features. Version also available without the radio component for expanding I/O points at an existing DAX Remote location.
Supports to up to 8 DAX Remotes.
Each Master discrete input is replicated on each Remote discrete output.
Discrete inputs from one or more Remote units are wired as active low to appear on Master discrete outputs.
Compatible with existing DDAA1000 8 bit mode Remote devices (8 bit analog only).
All Master analog inputs replicate on all Remote analog outputs.
Analog outputs are mapped via confi guration software from Remote analog inputs (0 to 4 total).
Address selected by internal dip switches.
With a DAX Master, a Remote can have addresses 0 to 7 (8 choices).
Compatible with existing DDAA1000 8 bit mode Master devices (8 bit analog only).
Remote analog inputs are mapped via setup to Master analog outputs (0 to 4 total).
^ Top of Page ^

| ^ Top of Page ^ | ||
| Products |
Features & Benefits | Focus Item | Product Selection Guides | Catalog | PDF Library | Order Information | FAQ | |
| Tech Resources |
Engineering Specifications | Articles & Technical Papers | Installation Information | |
| Partners |
GE Fanuc | Omron | Rockwell Automation | Schneider Electric | Siemens | Technology Partners | |
| Industries |
Security | Traffic | and other industry application notes and diagrams | |
| Sales Channels |
Distributors | System Integrators | OEMs | |
| News |
Tradeshows and Events | Press Releases | Newsletters | |
| About Us |
Overview | Jobs/Employment | Office Locations/Contact Information | |
|
||
| © 1996-2009 Data-Linc Group. All rights reserved. | ||
| 091015 |