modem manufacturer: SCADA applications for modem data communication modems Mexico, South and Central and Latin America AmericaSpanishChinese
Data-Linc modems, tech support, industry alliances, sales channels, trade shows, informationIndustriesHomeAbout usNewsSales ChannelsPartnerships/alliancesTechnical ServicesProducts
product indicatorList of Antennas and CablesNET620Ñ Serial to Ethernet BridgeList of Wire modemsList of Wireless modems
DSS High-Speed 900MHz OFDM modem802.11b WiFi Compliant 2.4 GHz DSSS Wireless ModemHybrid Ethernet-serial Modem for the 2.4 GHz ISM Band SRM6320Hybrid Ethernet-serial Modem for the 900MHz ISM Band SRM6220Industrial Wireless Serial FHSS 900 MHz radio modemIndustrial Wireless Ethernet FHSS 900 MHz radio modemIndustrial Wireless Ethernet chassis mount 900 MHz radio modemIndustrial Wireless Ethernet High Speed Broadband 900 MHz radio modem900 MHz Industrial Wireless Discrete/Analog Wireles Multiplexer and Signal Conditioners 900 MHz Industrial Wireless modemIndustrial 900 MHz Wireless discrete/analog I/O extenderIndustrial Wireless Serial FHSS 2.4 GHz radio modemIndustrial Wireless Ethernet FHSS 2.4 GHz radio modemIndustrial Wireless Ethernet chassis mount 2.4 GHz radio modem2.4 GHz Industrial Wireless Discrete/Analog Wireles Multiplexer and Signal Conditioners Industrial Wireless Ethernet FHSS 2.4 GHz ETSI CE Mark802.11b WiFi Compliant 2.4 GHz DSSS Wireless Modem802.11b WiFi Compliant 2.4 GHz DSSS Wireless PCMCIA Card Modem

Material handlinghydro-electric powerOil rig drillinggas pipelineminingforestry logging


Wireless I/O



DD1000/SRM & DDAA1000/SRM 900MHz Multiplexers

DD1000/SRM & DDAA1000/SRM 2.4GHz Multiplexers

DD & DDAA Applications


PlantLinc 580D & PlantLinc 580DDA 900MHz Short-range Multiplexers

PLR580 Applications


PlantLincTM 580D and 580DA Industrial Wireless I/O Extenders for the 900 MHz ISM Band

short-range Wireless RF serial radio modem

Data-Linc Group's PlantLinc PLR580 industrial wireless I/O extender for use with Plantlinc 5000 in the 900 MHz, license-free ISM band—available in Discrete and Discrete/Analog versions

Features

  • Cost effective wireless discrete and analog signal extender
  • Operates in the license-free 902 - 928 MHz band
  • Excellent noise immunity using robust frequency hopping technology
  • Maximum range of 4 miles (6.5 km) with unobstructed line-of-sight
  • Repeater modes provide longer distances or obstruction avoidance
  • Supports point-to-point or point-to-multipoint architectures
  • No wires to route or trenches to dig
  • Easy to implement; automatic start and restart

Data-Linc Group’s PlantLincTM 580 Wireless I/O Extenders offer the ability to economically transmit 4-20mA and discrete I/O signals without the cost or inconvenience of adding wires or additional devices. The PlantLinc 580 combines an analog/discrete signal digitizer with Data-Linc Group's short range PlantLinc industrial grade license free radio modem. The result is a cost effective, simple to implement wireless solution for I/O signal transmission up to 4 miles (6.5 km).

The PlantLinc PLR580D Wireless Discrete I/O Extender has eight discrete inputs and eight discrete outputs. The PlantLinc PLR580DA Wireless Discrete/Analog I/O Extender includes discrete signals plus eight analog inputs and eight analog outputs. The wireless extenders may be used in pairs for point-to-point signal transmission or in point-to-multipoint configurations, providing I/O signal transmission to multiple locations.

The PlantLinc RF section of the extenders operates in the license-free 902-928 MHz spread spectrum band and incorporates frequency hopping transmission techniques with 32-bit CRC error detection. The result is extremely reliable I/O communications even in high noise plant environments and at a range of up to 4 miles (6.5 km) with line-of-sight, using omni directional antennas. In the event of a communication link failure, discrete and analog outputs are software configurable.

PlantLinc 580 Wireless I/O Extenders are ideal for data acquisition and control applications such as tank level monitoring and pump control. Please consult with a Data-Linc Group Applications Specialist by phone at (425) 882-2206; fax your proposed application diagram to us at (425) 867-0865; or for review.

Industrial Applications

  • Field and factory floor discrete and analog signal communication for all industries
  • Wireless connection between instruments or controllers/relays and PLC or RTU analog/discrete input and output blocks
  • Water/Wastewater example - monitor tank levels with 4-20 mA analog signals and control pumps with contact closure discrete signals.

Download a printable pdf (962K) version of this PlantLinc 580 data sheet.
To read pdf files you need to have Adobe Acrobat Reader installed on your PC.

^ Top of Page ^



PLR580 Specifications

Included
Software CD & User Documentation
RS232 configuration cable
Test antenna. 0dBd
12 VDC wall power supply

System Configurations
Point-to-point
Point-to-multipoint (1 Master multi-dropped with up to 8 Remotes)

Channel Functions
Analog. 4-20 mA standard, 24VDC max. Internal 8 bit
A/D yields 2% accuracy of 4-20 signals
Discrete Input. Self sensing open/close circuit detection
Discrete Output. Open collector— sink to ground
12-24 VDC. 100 mA max per channel.

Operating Environment
Standard. 32° to 140°F (0° to 60°C)
Humidity. 0 95% non-condensing humidity

Connections
Antenna. Standard thread SMA female. 50 &omh;
Supplied bench test 0 dB antenna
Optional. External omni directional or yagi antennas available.

Analog (4-20 mA input and output):
9 position pluggable terminal blocks (PLR580DA only)
Pluggable terminal blocks standard wire size 12-26 AWG

Digital (Contact Closure input and output):
9 position pluggable terminal blocks
Pluggable terminal blocks standard wire size 12-26 AWG

Power: 2 pin Terminal Block

Radio Specifications
Range. 4 miles (6.5 km), line-of-sight distance using omni directional antennas
Output power. 200 mW maximum (+23 dBm)
Receive Sensitivity. –106 dBm @ 10-6 raw BER
Repeater. Repeating can be achieved by using a PLR5000 configured as a Repeater or a PLR580 configured as a Repeater/Remote.

Indicators
Power
CD Carrier Detect
Tx Transmit Data
Rx Receive Data
Status Error Status

Voltage and Current
Voltage: 12 VDC nominal, min 8, max 14 VDC
Current: 160 mA idle, 660 mA peak on transmit @ 12 VDC

Weight
1.65 lb (0.75 kg)

Shipping Weight
4 lb (1.82 kg)

Enclosure
Standard. 18-gauge steel with mounting flanges
(see diagram below)

^ Top of Page ^

Download a pdf (828K) print version of the PlantLinc 580 I/O Extender data sheet.



PlantLinc 580D and 580DA Versions

PLR580D
Discrete signal multiplexer with integral radio modem:
902 to 928 MHz license-free radio modem with 8 discrete Inputs and Outputs.

PLR580DA
Discrete and Analog signal multiplexer with integral radio modem: 902 to 928 MHz license-free radio modem with 8 discrete Inputs and Outputs as well as 8 analog Inputs and Outputs.



RF serial wireless i/o extender dimensional drawing

Specifications subject to change without notice.

P/N 155-09908-002
PlantLinc is a trademark of Data-Linc Group

Top of Page ^

Products

Features & Benefits | Focus Item | Product Selection Guides | Catalog | PDF Library | Order Information | FAQ
Tech Resources

Engineering Specifications | Articles & Technical Papers | Installation Information
Partners

GE Fanuc | Omron | Rockwell Automation | Schneider Electric | Siemens | Technology Partners
Industries

Security | and other industry application notes and diagrams
Sales Channels

Distributors | System Integrators | OEMs
News

Tradeshows and Events | Press Releases | Newsletters
About Us

Overview | Jobs/Employment | Office Locations/Contact Information

spacerChinesespacerEspañol

spacer
Data-Linc Group
3535 Factoria Blvd. SE, Suite 100 • Bellevue, WA 98006 USA
Tel (425) 882-2206 • Fax (425) 867-0865 •

© 1996-2009 Data-Linc Group. All rights reserved.
100818